DeKalb, Illinois 60115 813 E. Locust St. P.O. BOX 965
815-756-2741
800-435-4481
|
|
|
|
|
|
| USE or RHW or RHH |
Underground service entrance cable, copper or aluminum alloy conductor,
600 Volt, XLP Insulation
|
|
DESCRIPTION
Annealed, solid or stranded copper or aluminum alloy (EC1350) conductor, insulated with
an abrasion, moisture, and heat resistant
cross-linked polyethylene.
APPLICATION
Type USE or RHW or RHH conductors are used in air, conduit
or other approved raceways as specified in the National
Electrical Code. USE or RHW or RHH can be used as
underground service entrance cable, for direct burial at temperatures not
to exceed 75°C; or when used as RHW conductor,
temperatures are not to exceed 75°C in wet locations; or when used as RHH
in dry locations, conductor temperatures are not to exceed
90°C. 250 MCM and larger sizes may be installed in tray per
NEC Article 318. Conductor is rated 600 volts.
SPECIFICATION
Underwriters Laboratories Standard 44 (RHW or
RHH) Underwriters Laboratories Standard 854 (USE)
Federal Specification J-C-30. National Electric Code.
|
|
|
|
|
Copper |
Aluminum |
|
|
|
|
|
Weight |
Ampacity* |
Weight |
Ampacity* |
|
| Size (AWG) |
Stranding |
Insulation Thickness (Mils) |
Nominal Diameter (Inches) |
1000' (Lbs.) |
75°C Wet |
90°C Dry |
1000' (Lbs.) |
75°C Wet |
90°C Dry |
Standard Package |
| SOLID |
| 12 |
Solid |
45 |
.171 |
31 |
20 |
20 |
|
|
|
500' CTN 1000' RL |
| 10 |
Solid |
45 |
.192 |
44 |
30 |
30 |
|
|
|
500' CTN 1000' RL |
| 8 |
Solid |
60 |
.249 |
68 |
45 |
50 |
|
|
|
500' CTN 1000' RL |
| STRANDED |
| 12 |
7 |
45 |
.182 |
31 |
25 |
30 |
|
|
|
500' CTN 1000' RL |
| 10 |
7 |
45 |
.206 |
47 |
35 |
40 |
|
|
|
500' CTN 1000' RL |
| 8 |
7 |
60 |
.266 |
72 |
50 |
55 |
37 |
40 |
45 |
500' CTN 1000' RL |
| 6 |
7 |
60 |
.304 |
106 |
65 |
75 |
50 |
50 |
60 |
1000' RL |
| 4 |
7 |
60 |
.352 |
155 |
85 |
95 |
68 |
65 |
75 |
1000' RL |
| 2 |
7 |
60 |
.412 |
240 |
115 |
130 |
96 |
90 |
100 |
1000' RL |
| 1 |
19 |
80 |
.492 |
309 |
130 |
150 |
130 |
100 |
115 |
1000' RL |
| 1/0 |
19 |
80 |
.533 |
380 |
150 |
170 |
155 |
120 |
135 |
1000' RL |
| 2/0 |
19 |
80 |
.579 |
470 |
175 |
195 |
190 |
135 |
150 |
1000' RL |
| 3/0 |
19 |
80 |
.630 |
585 |
200 |
225 |
230 |
155 |
175 |
1000' RL |
| 4/0 |
19 |
80 |
.688 |
729 |
230 |
260 |
275 |
180 |
205 |
1000' RL |
| 250 |
37 |
95 |
.765 |
867 |
255 |
290 |
320 |
205 |
230 |
1000' RL |
| 300 |
37 |
95 |
.820 |
1029 |
285 |
320 |
375 |
230 |
255 |
1000' RL |
| 350 |
37 |
95 |
.871 |
1190 |
310 |
350 |
440 |
250 |
280 |
1000' RL |
| 400 |
37 |
95 |
.918 |
1350 |
335 |
380 |
495 |
270 |
305 |
1000' RL |
| 500 |
37 |
95 |
1.003 |
1670 |
380 |
430 |
605 |
310 |
350 |
1000' RL |
| 600 |
61 |
110 |
1.113 |
2010 |
420 |
475 |
715 |
340 |
385 |
500' RL |
| 750 |
61 |
110 |
1.218 |
2495 |
475 |
535 |
885 |
385 |
435 |
500' RL |
| 1000 |
61 |
110 |
1.372 |
3290 |
545 |
615 |
1145 |
445 |
500 |
500' RL |
| *Per NEC Table 310-16 |
|
|
|
|
|
|