| PRIMARY ALUMINUM UNDERGROUND DISTRIBUTION CABLE |
|
DESCRIPTION
1350, compressed-stranded aluminum conductor-semiconducting cross linked conduct
screen-.175ml, .220ml or 260ml cross-linked
polyethylene insulation-semiconducting
deformation-resistant polyethylene insulation shield-coated
copper concentric neutral conductor.
Triple-Tandom extruded and dry cored.
APPLICATION
To distribute power from substation to step-down transformer which in turn supplies power
to several homes or to small industrial and commercial customers.
SPECIFICATION
Aluminum Compressed Conductor is in Acc. With ASTM B-230, Class B, Insulation XLPE is in
Acc. with ICEA S-66-524, Part 3, Par. 3.7. Copper Tinned Wires are in Acc. with ASTM
B-33. Conducting Covering are in Acc. with ICEA
S-66-524, Part 4, Table 4a.
ALUMINUM U.D. CABLE
15KV .175 MIL XLPE
|
|
|
Diameter-Inches |
|
Metal Content |
Overall Jacket |
|
| Alum. Conductor Size/Stranding |
Coated Copper Neutral Stranding/Size |
Over Insulation .030 |
Over SemiCon .050 |
Net/Weight (Lbs.)/1000 Ft W/O Jacket |
Alum. |
CU |
Thick (Mils) |
Dia. (In.) |
Weight (Lbs.)/1000 Ft. With Jacket |
| 2-solid |
10 x #14 (Full) |
.660 |
.750 |
358 |
61 |
133 |
80 |
1.015 |
508 |
| *2-7 |
10 x #14 (Full) |
.695 |
.775 |
371 |
62 |
133 |
80 |
1.065 |
520 |
| 1/0-solid |
16 x #14 (Full) |
.730 |
.810 |
496 |
97 |
213 |
80 |
1.105 |
660 |
| *1/0-19 |
16 x #14 (Full) |
.770 |
.850 |
511 |
99 |
213 |
80 |
1.145 |
675 |
| *4/0-19 |
20 x #12 (Full) |
.920 |
1.000 |
875 |
199 |
425 |
80 |
1.330 |
1050 |
| Stock Items Standard Packaging #2-4/0 2500' Reels, 350-1000' Reels. Dimensions and weights listed are nominal and subject in standard industry tolerances. |
|
| Back to top of page |
|
ALUMINUM U.D. CABLE
15KV-133% Insulation Level .220 mil
|
| Alum. Conmductor Size/Strandig |
Coated Copper Neutral Stranding/Size |
Over Insulation .030 |
Over SemiCon .050 |
Net/Weight (Lbs.)/1000 Ft W/O Jacket |
Alum. |
CU |
Thick (Mils) |
Dia. (In.) |
Weight (Lbs.)/1000 Ft. With Jacket |
| 2-solid (Full) |
10 x #14 |
.760 |
.840 |
405 |
61 |
133 |
80 |
1.110 |
561 |
| 2-7 (Full) |
10 x #14 |
.785 |
.865 |
420 |
62 |
133 |
80 |
1.160 |
575 |
| 1/0-solid (Full) |
16 x #14 |
.825 |
.905 |
544 |
97 |
213 |
80 |
1.205 |
720 |
| 1/0-19 (Full) |
16 x #14 |
.860 |
.940 |
562 |
99 |
213 |
80 |
1.245 |
735 |
| 4/0-19 (Full) |
20 x #12 |
1.010 |
1.090 |
934 |
199 |
425 |
80 |
1.430 |
1125 |
|
| Back to top of page |
|
ALUMINUM U.D. CABLE
25KV-100% Insulation Level .260 mil
|
| Alum. Conductor Size/Stranding |
Coated Copper Neutral Stranding/Size |
Over Insulation .030 |
Over SemiCon .050 |
Net/Weight (Lbs.)/1000 Ft W/O Jacket |
Alum. |
CU |
Thick (Mils) |
Dia. (In.) |
Weight (Lbs.)/1000 Ft. With Jacket |
| 1/0 |
16 x #14 (Full) |
.940 |
1.020 |
0605 |
99 |
213 |
80 |
1.320 |
805 |
| 4/0-19 |
20 x #12 (Full) |
1.090 |
1.210 |
1005 |
199 |
425 |
80 |
1.550 |
1250 |
| Available upon request (Minimum Production Runs) 2 gauge 175mil Copper, 35K Primary Aluminum U.D. Cable (XLPE) |
| 15KV, 25KV and KV Primary Copper U.D. Cable (XLPE) 15KV, 25KV and 35KV Copper or Aluminum Power Cable. |
| *1/3 neutral and larger sites available upon request. |
|
|
|
|
|
|
NEHRING ELECTRICAL WORKS CO., DeKalb, Illinois 60115 - 815-756-2741 - 800-435-4481
|