DeKalb, Illinois 60115 813 E. Locust St. P.O. BOX 965
815-756-2741
800-435-4481
|
|
|
|
|
|
| COVERED ACSR SERVICE DROP CABLE |
|
ALL ALUMINUM HMW POLYETHYLENE OR XLP
DESCRIPTION
Either one, two, or three stranded all aluminum conductors covered with HMW polyethylene
or XLP twisted around a bare ACSR conductor.
APPLICATION
Used in the overhead transmission of power from pole to building weatherhead.
SPECIFICATION
ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes.
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors.
ASTM B-232 Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR).
ASTM D-1248 Polyethylene Plastics Molding and Extrusion Materials.
ANSI C-8.35 Specifications for Weather-Resistant Polyethylene-Covered Wire and Cable.
ICEA S-61-402
NEMA PUB NO. WC 5-1973 Standards Publication Thermoplastic Insulated Wire and Cable for
the Transmission and Distribution of Electrical Energy.
|
|
|
|
Weight (Lbs.)/1000 Ft. Total |
Standard Packaging |
| Code Word |
Size & Stranding |
Insul. Thick |
Aluminum Conductor |
Poly |
XLP |
Coils (FT.) |
Reels(FT.) |
| ACSR DUPLEX |
| Setter |
6-1 |
6-6/1 |
49 |
63 |
64 |
500 |
3300 |
| Shepherd |
6-7 |
6-6/1 |
49 |
75 |
77 |
500 |
3300 |
| Terrier |
4-7 |
4-6/1 |
79 |
115 |
117 |
500 |
2400 |
| ACSR TRIPLEX |
| Voluta |
6-7 |
6-6/1 |
73 |
116 |
118 |
1000 |
2200 |
| Whelk |
4-1 |
4-6/1 |
117 |
165 |
169 |
500 |
1700 |
| Periwinkle |
4-7 |
4-6/1 |
118 |
172 |
176 |
500 |
1500 |
| Scallop |
4-1 |
6-6/1 |
102 |
143 |
146 |
500 |
1700 |
| Strombus |
4-7 |
6-6/1 |
105 |
156 |
160 |
500 |
1500 |
| Conch |
2-7 |
2-6/1 |
188 |
261 |
267 |
500 |
1800 |
| Cockle |
2-7 |
4-6/1 |
165 |
227 |
233 |
500 |
1800 |
| Neritina |
1/0-7 |
1/0-61 |
299 |
419 |
430 |
500 |
1200 |
| Janthina |
1/0-7 |
2-6/1 |
262 |
365 |
376 |
500 |
1200 |
| Cenia |
1/0-19 |
1/0-6/1 |
299 |
416 |
428 |
500 |
1200 |
| Ranella |
1/0-19 |
2-6/1 |
262 |
362 |
372 |
500 |
1200 |
| Cavolinia |
2/0-7 |
1-1/6 |
328 |
451 |
462 |
- |
1500 |
| Runcina |
2/0-7 |
2/0-6/1 |
377 |
519 |
530 |
- |
1500 |
| Triton |
2/0-19 |
2/0-6/1 |
377 |
514 |
526 |
- |
1500 |
| Zuzara |
4/0-19 |
4/0-6/1 |
891 |
1178 |
806 |
- |
1000 |
| ACSR QUADRUPLEX |
| Chola |
6-7 |
6-6/1 |
98 |
153 |
158 |
0500 |
2100 |
| Hackney |
4-7 |
4-6/1 |
158 |
229 |
236 |
0500 |
1500 |
| Palimino |
2-7 |
2-6/1 |
251 |
346 |
355 |
- |
1800 |
| Standardbred |
1/0-7 |
1/0-6/1 |
396 |
557 |
573 |
|
1100 |
| Costena |
1/0-19 |
1/0-6/1 |
399 |
551 |
566 |
|
1100 |
| Grullo |
2/0-19 |
2/0-6/1 |
503 |
680 |
697 |
|
1500 |
| Appaloosa |
4/0-19 |
4/0-6/1 |
800 |
1042 |
1063 |
|
1000 |
|
| Back to top of page |
| 5kV SPACER CABLE-TREE WIRE |
|
ALUMINUM, XLPE, HMW LOW-DENSITY, OR HIGH-DENSITY POLYETHYLENE COVERED
DESCRIPTION
All aluminum or ACSR conductor covered with XLPE, HMW, or HD Polyethylene.
APPLICATION
Used for primary or secondary distribution
where space is limited. This is an uninsulated
conductor; covering is intended to prevent flashovers or
shorts with other objects.
SPECIFICATION
ICEA
ASTM B-230
ASTM B-231
ASTM B-232
ASTM B-498
|
|
|
|
|
|
Weight (Lbs.)/1000 Ft. |
| Size AWG or Cir Mils |
Stranding |
Covering (Mils) |
Cable O.D. (Mils) |
Rated Strength (Lbs.) |
XLPE |
HMW Poly |
HDPoly |
| ALL-ALUMINUM CONDUCTORS |
| 4 |
7 |
80 |
385 |
793 |
77.4 |
70.1 |
71.1 |
| 2 |
7 |
80 |
443 |
1,215 |
108.6 |
99.1 |
100.3 |
| 1 |
19 |
80 |
482 |
1,566 |
127.9 |
119.3 |
120.6 |
| 1/0 |
19 |
80 |
522 |
1,944 |
154.0 |
143.9 |
145.4 |
| 2/0 |
19 |
80 |
566 |
2,403 |
185.5 |
174.2 |
175.8 |
| 3/0 |
19 |
80 |
616 |
2,979 |
225.0 |
211.9 |
213.6 |
| 4/0 |
19 |
80 |
672 |
3,618 |
274.0 |
258.7 |
260.0 |
| 250 |
37 |
80 |
718 |
4,419 |
311.8 |
299.4 |
301.5 |
| 266.8 |
19 |
80 |
734 |
4,473 |
334.3 |
316.8 |
319.0 |
| 300 |
37 |
80 |
771 |
5,301 |
365.5 |
351.7 |
354.0 |
| 336.4 |
37 |
80 |
807 |
5,790 |
404.0 |
389.6 |
391.9 |
| 350 |
37 |
80 |
821 |
6,084 |
419.1 |
403.8 |
406.2 |
| 400 |
37 |
80 |
866 |
6,696 |
471.5 |
455.2 |
457.8 |
| 450 |
37 |
80 |
909 |
7,380 |
524.1 |
506.5 |
509.2 |
| 477 |
37 |
80 |
931 |
7,821 |
552.5 |
534.1 |
536.9 |
| 500 |
37 |
80 |
949 |
8,199 |
576.3 |
557.6 |
560.4 |
| ACSR CONDUCTORS |
| 4 |
6/1 |
80 |
410 |
1,767 |
100.2 |
94.6 |
95.8 |
| 2 |
6/1 |
80 |
476 |
2,708 |
144.5 |
137.5 |
139.0 |
| 1 |
6/1 |
80 |
515 |
3,373 |
174.8 |
167.0 |
168.7 |
| 1/0 |
6/1 |
80 |
558 |
4,161 |
211.9 |
203.2 |
205.0 |
| 2/0 |
6/1 |
80 |
607 |
5,035 |
285.5 |
248.6 |
250.7 |
| 3/0 |
6/1 |
80 |
662 |
6,289 |
316.2 |
305.0 |
307.4 |
| 4/0 |
6/1 |
80 |
723 |
7,933 |
387.9 |
375.2 |
377.9 |
| 266.8 |
18/1 |
80 |
769 |
6,536 |
386.9 |
374.2 |
376.9 |
| 266.8 |
26/7 |
80 |
802 |
10,735 |
463.1 |
450.5 |
453.2 |
| 336.4 |
18/1 |
80 |
844 |
8,246 |
474.9 |
460.5 |
463.6 |
| 336.4 |
26/7 |
80 |
880 |
13,395 |
571.0 |
556.9 |
559.9 |
| 397.5 |
18/1 |
80 |
903 |
9,443 |
552.2 |
536.5 |
539.9 |
| 397.5 |
26/7 |
80 |
943 |
15,485 |
665.2 |
649.7 |
653.0 |
| 477 |
18/1 |
80 |
974 |
11,210 |
651.4 |
633.9 |
637.6 |
| 477 |
26/7 |
80 |
1018 |
18,525 |
787.6 |
770.5 |
774.2 |
|
|
|
|
|
|
NEHRING ELECTRICAL WORKS CO., DeKalb, Illinois 60115 - 815-756-2741 - 800-435-4481
|